Daker DK Plus convertible UPS with battery – Single phase VFI – 3000 VA – 2700 W
#3 101 72
PRODUCT DESCRIPTION
Product characteristics
Convertible UPS with batteries Single phase
• The stated backup time in minutes is estimated and may vary according to the load characteristics, operating conditions and environment
• Nominal power: : 3000 VA
• Active power: : 2700 W
• Backup time: : 7 min
• Weight: : 30 kg
General characteristics
DAKER DK PLUS – On-line double conversion UPS (rack/tower) – single phase and three phase VFI
• The main parameters of the UPS, including the battery charge level and faults, are displayed on the LCD screen on the front panel
• The integrated communication software not only controls the UPS and its switch-off if there is a malfunction, and enables the user to test the main functions remotely, communicate via SNMP/Internet/network adaptor and access the functions of the UPS via the Internet, but can also send the user an SMS if specific events occur
• The internal extension connector enables aWEB/SNMP card or a relay interface to be installed which provides insulated contacts for applications on industrial control panels or remote alarm panels
• If there is an electronic fault, overload, overheating or for scheduled maintenance operations, the automatic or manual (optional) bypass ensures continuity of the power supply for critical loads. A bypass switch is available for maintenance
Specifications UPS Legrand Single Phase (3 101 72)
General Features
• Nominal power (VA) 3000
• Active power (W) 2700
• Technology On-Line Double Conversion VFI-SS-111
• Waveform Sinusoidal
• UPS architecture convertible tower and rack 19
• Surge Rating 1530
• ECO Mode efficiency %98
Input
• Input voltage : 230 V
• Input frequency : 50-60 Hz ±5% Autosensing
• Input Voltage Range : 180-300 on full load, 150-300 on 80%load, 110-300 on 60% load
• THD Input current : < 3%
• Input power factor : > 0.99
• Input Plug : 3 101 72: Multi Standard, 3 100 75: British Standard
Output
• Output voltage : 230V ± 1%
• Output frequency (nominal) : 50/60 Hz (can be set from the LCD panel) +/- 0.1%
• Crest Factor : 1:3
• THD Output voltage : Linear load 2% Nonlinear load 5%
• Output Voltage Tolerance : ±1%
• Bypass : Internal automatic Bypass (included), External maintenance Bypass (OPTIONAL)
Batteries
• Uptime Expansion : yes
• Number of batteries : 6
• Battery series Type/Voltage : 12V 9Ah
• Uptime with 80% load (min) : 8
• Recharge time (to 100%) : 4 hours
• attery disconnector for safe transportation : yes
Communication and management
• Display and Signals : Four buttons and four LEDs to monitor the status of the UPS in real time
• Communication Ports : RS232 serial ports, USB
• Remote Management : available
• Network interface slot : SNMP
Mechanical features
• Measurements H x L x D (mm) : 440×88 (2U) x600
• Battery Cabinet Measurements H x L x D (mm) : 440×88 (2U) x600
• Net Weight (kg) : 30
Environmental conditions
• Operating temperature (°C) : 0 ÷ 40 °C
• Degree of protection : IP20
• Relative humidity (%) : 0-95% non-condensing
• Noise level at 1 m (dBA) : On-Line Mode < 50, Eco Mode < 40
• Heat Loss (BTU/h) : 818
Certifications
• Standards : EN 62040-1, EN 62040-2, EN 62040-3